Send Message
Home ProductsRefrigeration Service Valves

Pisto EVR Solenoid Valve

Pisto EVR Solenoid Valve

  • Pisto EVR Solenoid Valve
  • Pisto EVR Solenoid Valve
  • Pisto EVR Solenoid Valve
  • Pisto EVR Solenoid Valve
Pisto EVR Solenoid Valve
Product Details:
Place of Origin: China
Brand Name: Original
Certification: CE/ROHS/FCC/SGS
Model Number: EVR series
Payment & Shipping Terms:
Minimum Order Quantity: 20 pcs
Price: negotiate
Packaging Details: cartons
Delivery Time: 4-6 weeks
Payment Terms: T/T
Supply Ability: 2000pcs per weeks
Contact Now
Detailed Product Description
Packing: Individual Box Material: Copper
Condition: Brand New Application: Condensing Unit
Name: Solenoid Valve Fuction: Control Flow
High Light:

HVH EVR Solenoid Valve

,

Pisto EVR Solenoid Valve

,

Open Type EVR Solenoid Valve

HVH Piston Twice Open-Type Solenoid Valve Of Refrigeration / Air Conditioning System,For Refrigeration Unit

 

Description:

 

·Model HVH piston type solenoid valve is a twice open-type solenoid valve to be suitable to one-way flow.

 

·Model HVH piston type solenoid valve is used on the liquid, air suction and hot vapor pipes of the refrigeration, cold storage and air conditioning facilities.

 

·The coil of varies voltages is available for Model HVH piston type solenoid valve with a universal valve body.

 

·Model HVH piston type solenoid valve could be supplied in whole or in split, that means valve body and coil could be supplied separately.

 

Specifications:

 

Model Size △P(bar) Max Operating Pressure(bar) Kv(㎥/h)
Weld Connection Min. MOPD LiquidMOP
HVD25 1-1/8ODF 0.2 31 45 10
HVD32 1-3/8ODF 0.2 31 45 16
HVD40 1-5/8ODF 0.2 31 45 25

 

 

1) Kv value: The flow rate (m³/h) of water of density 1t/m³ passing through the solenoid valve with the pressure differential of 100 KPa.

2) The MOPD of gaseous medium is about 1 bar higher than that of liquid.

 

 

Model Nominal Refrigerating Capacity kW
Liquid Air Suction Hot Vapor
R22/R407C R134a R404A/R507 R22/R407C R134a R404A/R507 R22/R407C R134a R404A/R507
HVD25 201.0 186.0 141.0 22.80 16.30 20.40 92.30 73.20 75.30
HVD32 322.0 297.0 255.0 36.50 26.10 32.60 148.00 117.00 120.00
HVD40 503.0 464.0 351.0 57.00 40.80 51.00 231.00 183.00 188.00

 

 

The working condition the nominal refrigerating capacity of liquid and air suction is as follows:

 

Evaporation Temperature: te = -10℃;

Liquid Temperature before Valve: t1 = +25℃;

Pressure Drop after Solenoid Valve: △P = 15KPa

 

The working condition the nominal refrigerating capacity of hot vapor is as follows:

Condensation Temperature: tc = +40℃;

Pressure Drop after Solenoid Valve: △P = 80KPa;

Hot Vapor Temperature: th = +65℃;

Liquid Refrigerant Overcooding: △t = 4K

 

 

 

Technical Parameters:

 

Applicable Refrigerants: HCFC or HFC(Customer apecified)
Applicable Medium Temperature: -30℃~+105℃
Application Ambient Temperature of Solenoid -40℃~+65℃
Standard Voltage of Solenoid AC 380V,AC 220V/50Hz(Customer design is available)
Allowable Voltage Fluctuation for Solenoid +10%~15%
Connection of Solenoid Standard 3-wire insert connector
 
Pisto EVR Solenoid Valve 0
 
Should you have any question, feel free to contact.

Contact Details
Shenzhen Sino-Australia Refrigeration Equipment Co., Ltd.

Contact Person: Jason

Tel: 86-13480948557

Fax: 86-755-82209876

Send your inquiry directly to us (0 / 3000)